Online calculators give a rough figure by dividing a load by a power factor — but they miss the things that actually govern the size, like motor starting, non-linear loads and site derating. That's why they so often get it wrong. We'd rather size it with you properly: send us your load and application and we'll give you a figure you can rely on.
It depends on your total running load, the largest step load (usually a motor starting), the load character and your resilience requirement — not floor area or a single headline figure. The reliable way to get the answer is a proper load schedule, which we'll build with you.
kW is real power (the work done); kVA is apparent power (what the alternator must supply). They're related by power factor: kVA = kW ÷ pf. Generators are rated in kVA at 0.8 power factor, so a 400 kW load at 0.8 pf needs a set rated for 500 kVA.
Significantly. A motor started direct-on-line draws an inrush of typically 6–7 times its full-load current for a few seconds, and the set must hold voltage and frequency within limits while it accelerates. This transient is often the single biggest factor in sizing. Star-delta, soft starters and VSDs reduce it.
Yes. Healthcare premises are designed to HTM 06-01, which sets out resilience requirements for the electrical supply — secondary supplies, fuel autonomy, segregation of essential services and rapid changeover. Life-safety circuits often need fire-resistant cabling (BS 8519) and no-break supplies via UPS.
More than most people expect. A radiator-cooled set moves large volumes of cooling air, plus combustion air for the engine and a path for radiated heat. Inadequate ventilation raises intake temperatures and forces the set to derate — so a correctly sized generator can still underperform in a poorly designed plant room.