330kVA Perkins Diesel Generator


Key features:
The Cat XQP310 is a 310 kVA (248 kW) Stage V diesel generator designed to provide robust 50 Hz three-phase power for large UK sites. It is powered by the Cat C9.3B turbocharged-aftercooled engine, which combines high output, strong fuel efficiency and a compact footprint for straightforward installation. This set is ideal for industrial, commercial and construction users who require dependable, low-emission power at standard 400/230 V.
The generator is mounted on a heavy-duty steel baseframe that incorporates a dual-wall fuel tank sized for around 12 hours of runtime at 75% prime load. Integrated skid plates, drag points and forklift pockets make handling and positioning the unit easier on busy sites. The dual-wall design provides 110% containment of on-board fluids, with a bund level alarm to support environmentally responsible operation.
An XQCP digital controller manages the engine and alternator while providing comprehensive power metering and event logging. The front panel offers a clear interface, emergency stop and configurable alarms and shutdowns to help protect both the generator and connected equipment. Two-wire remote start/stop terminals and AC auxiliary power connections allow straightforward integration with automatic transfer switches for standby or mains support use.
The XQP310 uses an LC5114N brushless, self-excited alternator with Class H insulation, IP23 protection and coastal insulation treatment. A three-phase sensing AVR provides adjustable volts-per-hertz regulation and maintains stable output under varying loads. The 12-lead winding supports flexible three-phase reconnection, with low total harmonic distortion suitable for many sensitive loads.
The galvanized, powder-coated enclosure is acoustically treated with precision-cut insulation to deliver low external noise levels around the generator. This makes it suitable for operation near workplaces, industrial premises and some commercial locations where noise is a concern. The engine and aftertreatment system are engineered to meet stringent EU Stage V emissions limits and are specified for ultra low sulphur diesel with approved biodiesel blends.
This 310 kVA generator is suited to industrial plants, data and utility sites, large construction projects and event power where a strong three-phase supply is required. It can also function as a main standby generator for sizeable buildings or critical process loads when installed with appropriate switchgear and distribution.
View Full Specifications Sheet
| Engine manufacturer | Cat |
| Model | C9.3B |
| Cylinder configuration | Inline 6-cylinder, 4-stroke-cycle, water cooled, diesel |
| Number of cylinders | 6 |
| Displacement (L) | 9.3 |
| Aspiration | Turbocharged-aftercooled (TA) |
| Speed governor | Electronic ECM controlled (A6E2) |
| Cooling system | Water cooled radiator with vertical air discharge, variable speed fan |
| Lubrication oil capacity (L) | 30 (oil pan) |
| Electrical system (VDC) | 24 |
| Speed / Frequency | 1500 rpm / 50 Hz |
| Engine gross power (Prime 50 Hz) kW | 248 (generator prime rating) |
| Fuel | Diesel, ultra low sulphur diesel (ULSD) to EU Stage V specification |
| Starting system | Electric start with 24 V DC charging alternator |
| Prime power (kVA) | 310 |
| Prime power (kW) | 248 |
| Width (W) mm | 1514 |
| Length (L) mm | 4085 |
| Height (H) mm | 2226 |
| Weight (kg) | 4784 with fuel, lube oil and coolant |
| Fuel tank capacity (L) | 667 |
| Frequency (Hz) | 50 |
| Voltage (V) | 400/230 |
| Power factor (cos ϕ) | 0.8 (three-phase rating) |
| Phase | 3 |
| No. of phases | 3 |
| Voltage (V) | 400/230 |
| Frequency (Hz) | 50 |
| Power factor (cos ϕ) | 0.8 |
| Poles | 4 |
| No. of bearings | Single, close coupled |
| No. of leads | 12-lead, reconnectable |
| Insulation class | Class H |
| Degree of protection | IP23 drip proof |
| Excitation system | AVR controlled, brushless, self-excited |
| Connection type | 3-phase reconnectable (via 12-lead scheme) |
| Fuel consumption 100% Prime 50 Hz (L/h) | 62.6 |
| Fuel consumption 75% Prime 50 Hz (L/h) | 46.9 |
| Fuel consumption 50% Prime 50 Hz (L/h) | 32.9 |
| Estimated runtime at 75% load (h) | 14.2 with standard tank |
| Noise pressure level @ 7 m dB(A) | Approximately 65.4–67.2 at 75–100% load with enclosure |
Delivery information
Warranty information
Solent Power Ltd (Company Number 12622565) is a company registered in England and Wales. Our registered office is located at Station yard, Bowes Hill, Rowlands Castle PO9 6BP. VAT No. 363504018